Instrumentation, Transmitter - Universal HART
|
|
|
Input
- Resistance thermometer (2, 3, 4 wire circuit) or Thermocouples
- Resistance remote signalling unit (0...5000 OHMS)
- Voltages, mV (–125...+1200 mV)
Output
- 2 wire technique 4...20 mA, HART signal
Electrical isolation (I/O)
Measured error 0.1 K
Customer-specific linearization with up to 32 tie points
Continuous sensor and self-monitoring
- Parameter saved permanently in EEPROM
- Monitoring of data integrety every 10 s
- Wire break monitoring in acc. with NAMUR NE 89
Substitution strategy in case of error (NE 43)
Approvals for explosion protection, Intrinsically safe
- II 2 (1) G EEx [ia] ib IIC T6, mount in zone 1
- II 3 G EEx n A II T6, mount in zone 2
Input functionality (absolute, differential, average value)
EMC acc. to EN 50082-2 and NE 21
Parameterization
- Device Management Tool: SV401 (SMART VISION)
- Hand held terminals: 691HT, STT04, HHT275
- CoMeter (HART configurator/LC display)
5 years warranty
|
 |
|
The TH02 is a 4...20 mA loop-powered transmitter for RTD and Thermocouple sensors.
Any 2-, 3- or 4-wire RTDs or Thermocouples of any common type may be used.
The cable resistance can be manually configured as well.
Using a PC, the Windows-based Smart-Vision HART communications software and a compatible FSK modem may be used for configuring the unit.
The wide range of parameters can be configured via the above software or a HART communicator: TAG no., sensor type, number of wires, cable resistance, error detection level, measuring range/unit, damping, offset and status indication, etc.
The TH02 is embedded in silicone which makes it resistant to humid environments.
The TH02 is fitted in a DIN B housing, has a 6 mm center hole for quick sensor replacement.
The spring loaded mounting screws ensure a safe fastening even in vibrating environments.
Additional information: Data Sheet.
|
|
|